Operating Instructions

22

3.5.2 UPS Configuration Screen

Review Settings

Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing

and

to review the settings.

Main Menu

UPS Status

> UPS Configuration

Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools

UPS Configuration

UPS Configuration
> Review Settings

Change Settings
Service Mode

Review Settings

Voltage
Frequency
Battery
Alarm
Service Contact
Auto Restart
UPS Shutdown Delay
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Battery Ca.
Air Filter Reminder
Guarantee Shutdown

External Battery

External batt config
Amp.Hr

0000

Charge (A) 00.0

Bypass Alarm Mode

Bypass Alarm Mode
Mode:

Enable

Intelli-Battery Ca.

Intelli-Batteries

0

Air Filter Reminder

Air Filter Reminder
Mode:

26 weeks

Guarantee Shutdown

Guarantee Shutdown
Mode: Enable/Disable

Voltage

Voltage Settings

Input 208/120
Output 208

Frequency

Frequency Settings
Frequency Hz: 60
Sync Range Hz: +/- 5.0
Slew Range Hz/S: 3.0

Battery

Battery Settings
Test intrvl weeks: 2
on Wed 06:00
Low Batt Warn:2 min

Alarm

Alarm Settings
Redundant Alarm:

Enabled/Disabled

Max Load: Enabled/Disabled

Service Contact

Service Contact
Liebert Corp.

www.liebert.com

Auto Restart

Auto Restart
Mode:

Disable

Batt %

0%

Delay

10

UPS Shutdown Delay

UPS Shutdown Delay
120 seconds

Remote Shutdown

Remote comm shutdown
Mode: Enable

Review Settings menu options