Change Configuration Settings - Change Settings Menu

Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration

screen, select the Change Settings option. You may configure Nfinity from a large variety of selec-

tions. Items indicated by an asterisk (*) are the selected settings.

Input Voltage: Select the required input voltage set-

ting. This voltage must match the bypass voltage

jumper setting.

Display Voltage: Displays the actual voltage the

unit is configured for.

Frequency Sync Range: Sets the window to which

the system synchronizes to the input supply.

Frequency Slew Rate: Sets the rate of change of

frequency through the sync range window.

Set Password: Set a Password to prevent unautho-

rized users from changing the configuration of the

Nfinity. It can be up to seven characters in length.

Once set, the password will be required to change the

configuration.

Main Menu

UPS Status

> UPS Configuration

Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools

UPS Configuration

UPS Configuration

Review Settings

> Change Settings

Service Mode

Change Settings

Input Voltage
Display Voltage
Frequency Sync Range
Frequency Slew Rate
Set Password
Auto Battery Test
Low Battery Warning
Auto Restart
User Settings
Set Date/Time
Max Load Alarm Set
UPS Shutdown Delay
Redund Alarm Set
Service Contact
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Batt Ca.
Air Filter Reminder
Guarantee Shutdown
Line Compensation
Factory Defaults

Input Voltage
* 208/120

240/120

Display Voltage

208

* 240

Frequency Sync Range

0.5 Hz
1.0 Hz
2.0 Hz
3.0 Hz
4.0 Hz

* 5.0 Hz

NOTE
If the password is lost, call Liebert Technical

Support.

Frequency Slew Rate

0.5 Hz
1.0 Hz
2.0 Hz
3.0 Hz
4.0 Hz

* 5.0 Hz

Set Password

xxxxxxx