2 adding or replacing modules, 3 replacing the user interface, Adding or replacing modules – Emerson Nfinity 208 User Manual

Page 39: Replacing the user interface

Advertising
background image

Troubleshooting

35

4.3.2 Adding or Replacing Modules

1. Lift module to appropriate bay, resting end of module on bay

shelf. Use caution not to rest the module on the lower bezel

cover.

2. Push module into bay. Once halfway in, slide module sideways

toward the center of the UPS. Continue pushing module until

fully inserted.

3. Press and turn fastener clockwise until locked. If replacing a

Control or Power Module, press lever down.

4. Wait about 15 seconds as the module performs a start-up test

and synchronizes with the other modules. Both the yellow and

green LEDs should be flashing. A green flashing LED will

then confirm the module is properly installed.

5. If UPS was placed in bypass manually, transfer back to UPS

operation.

6. Replace bezels.

4.3.3 Replacing the User Interface

1. Lift off user interface and set it on top

of the UPS frame.

2. The attached cable will be connected to

an Intellislot card, found in a port

between the control modules.

3. Remove the cable and the attached

Intellislot card from the UPS.

4. Plug the new Intellislot card into the

UPS.

5. Plug the new user interface cable into

the Intellislot card.

6. Set replacement User Interface into

proper position.

NOTE
Power Modules must be installed in the top half of the Nfinity frame. Battery Modules can be

installed in any bay of the UPS frame.

NOTE
When replacing the Control Module, record user configuration data before removing. Re-verify

the configuration settings after the new Control Module is installed.

Turn fastener

clockwise

Press lever down (for

Control and Power Modules)

Advertising
This manual is related to the following products: