Basic flue venting (residential only), A. single heater venting, Example – Enerco HST45 User Manual

Page 13

Advertising
background image

13

Operating Instructions and Owner’s Manual

| Gas-Fired Low-Intensity Infrared Heater

The seams along the length of the piping and the joints between
sections of piping should be sealed to prevent a potential
leakage of flue gas into building. Use 100% RTV Silicone Rubber
Adhesive sealant suitable for 500°F.

6. All portions of the vent pipe shall be supported to prevent

from sagging.

7.

When the vent pipe passes through areas where the ambient

temperature is likely to induce condensation of the flue gasses,
the vent pipe should be insulated and a condensation drain
should be provided.

8. The minimum clearance to combustible materials for single-

wall flue pipe shall be 6 inches. This may be reduced when the
combustible material is protected as specified in the National
Fuel Gas Code or the authority having jurisdiction.

9.

Single-wall metal pipe shall not originate in any unoccupied

attic or concealed space and shall not pass through any attic,
inside wall or concealed space, or through any floor.

10. A venting system shall terminate at least 3 feet (0.9m) above

any forced air inlet located within 10 feet (3.1m).

b) Vent Termination (Residential Installations)

1. The vent terminal shall terminate above the roof line so that no

discharge opening is less than 2 feet (0.6m) horizontally from
the roof surface. The lowest discharge opening will be no closer
than the minimum height specified in the following table.
These minimum heights may be used provided the vent is not
less than 8 feet (2.4m) from any vertical wall or similar
obstruction.

BASIC FLUE VENTING (Residential Only)

Venting must be in compliance with the latest edition of the

National Fuel Gas Code (ANSI. Z223.1 latest edition: or the
authority having jurisdiction.

Uninsulated single-wall metal pipe shall not be used outdoors in

cold climates for venting of these heaters as specified by Section
7.8 of the ANSI Z223.1/NFPA 54 National Fuel Gas Code-latest
edition.

For the installation of a single-wall metal pipe through an exterior

combustible wall, refer to the latest edition of the National Fuel
Gas Code or the authority having jurisdiction.

In regions of the country where prevailing winds are consistently

higher than 40 mph, it may be necessary to terminate the vent
system above the roof level.

Other venting references can be found in equipment volume of the
ASHRAE Handbook.

A. SINGLE HEATER VENTING

a) Vertical Through the Roof

NOTE: For residential applications, the heater must

not be connected to a separate chimney,
but must be installed using the venting
system as specified below.

1. When venting the heater to outside of building through a roof,

use 3 inch O.D. single-wall metal pipe. This is to be constructed
of galvanized sheet metal or other approved noncombustible,
corrosion-resistant material as indicated by state and/or local
codes.

2. A vent passing through a combustible roof shall extend through

a 2-inch clearance roof thimble. Double-wall, Type B vent must be
used for the portion of the vent system which passes through
the roof. An approved vent cap (such as Leslie “VersaCap” Type
B) must be attached to the end of the flue.

3. The maximum equivalent length of vent pipe should be carefully

observed. A safety switch in the heater is designed to shut the
heater off before excessive flue restriction causes bad
combustion.

Minimum Equivalent Length = 5 feet of Pipe

Maximum Equivalent Length = 25 feet of Pipe

Use the following correction factors to obtain the equivalent length:

a) A horizontal run is equal to 15 feet of vent length.

b) An approved vent cap is equal to 10 feet of vent length.

c) For each elbow in the first 15 feet of run, they are equal to
10 feet of vent length.
d) For each elbow past the first 15 feet of run, they are equal to
15 feet of vent length.

4. Limit the quantity of 90° elbows to two. When vent pipe is in a

horizontal run, it must rise not less than ¼ inch per foot from
the start of the vent system towards the vent terminal.

5. Joints between sections of piping shall be fastened by sheet

metal screws or other approved means.

SINGLE HEATER VENTING

Vent Cap

(Leslie VersaCap)

Type B

2' Min.

2' Min.

(when no wall or

parapet exist)

10'

or less

Flashing

2" Clearance Thimble

Seal joint &
annular space.

4"

Vent

Dia.

Total Vent

Height

(5' Min.)

¼ per ft. rise

Lateral

VERTICAL

THROUGH THE ROOF

2' Min.

(when no wall or

parapet exist)

H (Min.)

Not less than 8ft.

2ft. min.

ll

a

W l

aci

tr

eV

for an approved vent cap you have ---------10 ft.

for a horizontal run you have -----------------15 ft.

Your Maximum Equivalent Length is ---------------- 25 ft.

EXAMPLE

Enerco Group, Inc.,

Advertising