Table 3: RJ Interconnect Maximum Current

QCPort Interconnect Cable

Allowable Current

10 [25] inch [cm]

1.0 A

3 [1] feet [meter]

1.0 A

6 [2] feet [meter]

1.0 A

10 [3] feet [meter]

1.0 A

The voltage range between +24 and G must be between 18 and 28V DC.

Locating a Power Supply

The QCPort interconnect system allows several options for supplying power, as outlined
in this section. To determine which option meets your needs, consider the distribution of
the loads, power supply location, and the number of power supplies used. Power
supplies must be 24 volts.

Notice

In the United States and Canada, the power supply must also be Class 2.

Warning

Whenever two or more power supplies are connected to the same segment, the
ground for the system must be referenced to only one point.