background image

Intelligent Technologies QCPort System Install Manual

November 2005

MN05001002E

For more information visit

www.eatonelectrical.com

Page

20

1 Power Supply

Locate the power supply at the end, middle, or anywhere along the cable, as illustrated in
the following figure.

Figure 12: 1 Power Supply

Grounding the Interconnect System

You must ground the QCPort system at only one location.

Warning

If you use more than one power supply, all of them should be attached to the same
earth ground.

Ground the G conductor at only one place at the power supply that is closest to the
physical center of the QCPort system to maximize the performance and minimize the
effect of outside noise.

To ground QCPort:

• Connect the G wire to earth ground using a 1 in (0.25 mm) copper braid or a #8

AWG wire up to 10 ft (3 m) maximum in length.

• Use the same wire to connect the power tap to earth ground.