Instruction Manual for the Eaton RTC-50

Automatic Transfer Switch Controller

26.

Utility - Monitoring and Protection

This feature provides Utility monitoring and protection

functions. If the Utility power source fails, then the RTC-

50 will begin the sequence of operations necessary to

transfer the load circuit to the Generator power source.

All Feature 26 monitoring and protection functions are fail-

safe operations.

26D. Go To Generator

This feature provides the capability for an external contact

closure to initiate a transfer from Utility to Generator.

After the Generator becomes available, TDNE will time out

before the transfer to Generator takes place. Re-transfer

will occur when the external contact is opened or under a

failsafe condition. A connection point for the connection

of an external contact is provided.

26P. All Phase Undervoltage Protection

Dropout: 168 Vac (70% of 240 Vac nominal)

Pickup: 192 Vac (80% of 240 Vac nominal)

SECTION 2:HARDWARE DESCRIPTION

2.1 General

The purpose of this section is to familiarize the reader with the

RTC-50 controller hardware, its nomenclature, and to list the

unit’s specifications.

2.2 LED Indicators

Utility Available

The green Utility Available LED illuminates if the utility power

source meets the criteria to be considered “available”. That is,

when it is within its undervoltage range.

Generator Available

The red Generator Available LED illuminates if the generator

power source meets the criteria to be considered “available”.

That is, when it is within its undervoltage range.

2.3 Programming Jumpers

The RTC-50 controller is programmable via two jumpers on the PC

board. The jumper selections are discussed in Section 4, Program-

ming.

Figure 1. RTC-50 Connectors and Programming Jumpers.

2.4 Input/Output Connectors

Located along the bottom of the RTC-50 are connectors J1, J2,

J3, and J4. J1 and J2 provide for voltage monitoring of utility.

J3 and J4 provide for voltage monitoring of the generator.

Located along the top of the RTC-50 are connectors J6, J7, and

J8. J6 provides connections for the control input and the transfer

switch control outputs. J7 provides load shedding connections

for the customer to use. J8 provides connections to a remote

light to indicate that generator service is due. A pushbutton can

be wired to the Reset Switch input to acknowledge and reset the

Generator Service indication.