APPENDIX A: OPERATIONAL FLOWCHART

Utility is available

Is Generator

available?

N

ATS connects to Utility

(Utility Close Output closes)

TDNE timer times out

(20 sec or 50 sec)

Transfer to Generator

(Gen Close Output closes)

Y

Generator is powering the load

TDEN timer times out

(10 sec)

N

Is Utility

available yet?

Y

Utility is powering the load

Utility is powering the load

Generator shuts down

Transfer to Utility

(Utility Close Output closes)

Is Utility

available?

Y

N