Clearances (continued), Mantel clearances with hood, Floor clearance – Empire Comfort Systems VFSR-24-3 User Manual

Page 10: Sidewall & ceiling clearances, Mantel clearances without hood

Advertising
background image

26333-3-1210

Page 10

Mantel clearances with Hood

(Figure 5)

You must have non-combustible materials above the fireplace

opening. Non-combustible material must extend at least 8" above

fireplace opening. With sheet metal, you must have non-combustible

material behind it.
Heat resistant materials such as slate and marble must be

at least

1/2" thick. Sheet metal should not be installed onto combustible
material.
Example:
A mantel may project from the wall a maximum of 2" at a

minimum of 13-1/2" above the opening, and a maximum of 6" at a

minimum of 15" above the opening.

Figure 5

If your installation does not meet the above minimum clearances,

you must proceed to one of the following steps:

Operate the heater with the flue damper open. See page 11

for

Installing as a Vented Appliance.

Raise the mantel to the proper height.

Remove the mantel.

Floor clearance

(Figure 6)

If installing heater at floor level, the minimum distance to combus-

tibles is “0” inches.

Figure 6

Sidewall & ceiling clearances

(Figure 3)

Figure 3

The sides of the fireplace opening must be 6" from any combustible

wall. The ceiling must be at least 36" (for the 16" log) and 41" (for

18", 24" and 30" logs) from the fireplace opening.

Mantel clearances without Hood

(Figure 4)

You must have non-combustible materials above the fireplace

opening. Non-combustible material must extend at least 12" above

fireplace opening. With sheet metal, you must have non-combustible

material behind it.
Heat resistant materials such as slate and marble must be

at least

1/2" thick. Sheet metal should not be installed onto combustible

material.

Figure 4

If your installation does not meet the above clearances, you must

proceed to one of the following steps:

Use a hood

Operate the heater with flue damper open. See page 11 for

Installing as a Vented Appliance.

Raise the mantel to the proper height.

Remove the mantel.

cLeArANceS (continued)

Non-combustible

Material Distance

requirements for Safe Installation

12" or more

Non-combustible material

Less than 12"

Non-combustible material must be ex-

tended to at least 8" with the installation

of the optional fireplace hood. If you can-

not extend non-combustible material at

least 8", you must operate heater with

flue damper open.

HEATER IN FIREPLACE

OR FIREBOX

COMBUSTIBLE

MATERIAL