Figure 91 warning history, Figure 92 fault history, 2 warnings – Emerson Series 600T User Manual

Page 91: Figure 93 warning screen, Warnings, Charge

Advertising
background image

Troubleshooting

79

Figure 91 Warning history

Figure 92 Fault history

The warnings, fault meanings and possible causes in the following text and in Table 15 may be used

in troubleshooting the messages and may also aid in identifying conditions outside the flywheel sys-

tem that may adversely affect it.

8.2

Warnings

A Warning is an indication of an abnormal system condition significant enough to warrant being

annunciated and logged. Warning conditions may indicate that a system parameter is out of its nor-

mal operating range, or may signal an external problem. A Warning indication is for information only

and does not require any operator intervention for continued operation of the unit. While in Warning

condition, normal operation of the unit will continue unimpeded. A warning can indicate an operating

condition that warrants observation and may require preventative maintenance.

Figure 93 Warning screen

The Warning condition is indicated by the System Status field displaying “WARNING” in the Control

Panel window (see Figure 93). If one Warning is present, the Warning Label (see Table 15.) will be

displayed.
While the Warning condition exists, and if more than one Warning is present, F5 the “More Info” key

will be enabled in the Control Panel window. If pressed, the separate Warning Labels will be dis-

played in the Control Panel window.
Any of eight warnings could occur while the Liebert FS is operating. Warnings give advance alert of

potential problems and schedule service and preventive maintenance. These can be monitored and

investigated through the use of data from the Control Panel and system tests.

NEXT DONE

01 03/10/05 11:43 W
02 03/10/05 10:37 W
03 02/24/05 04:03 W
04 01/30/05 23:22 W
05 12/20/04 13:45 W
06 11/13/04 07:28 W
07 09/30/04 16:23 W

AUX POWER LOW
VIB INOPERATIVE
OVERSPEED
STATOR HOT
ROTOR HOT
RUNOUT
VACUUM

NEXT DONE

01 03/10/05 11:43 F
02 03/10/05 10:37 F
03 02/24/05 04:03 F
04 01/30/05 23:22 F
05 12/20/04 13:45 F
06 11/13/04 07:28 F
07 09/30/04 16:23 F

CURRENT OFFSET
CHECKSUM
SOFTWARE OV
DC BUS OV
SPARE OPEN
INTER PROCR COMM
MISER

RESET

MODE:

STATUS:

D

V

U

C

RPM:
SOC:
SOC:
BUS:
PWR:

39562

45.4%

538V

32.3kW

CHARGE

2 WARNINGS

SHUTDN

MORE

MENU

Liebert FS

LOCK

More information

Button (F5)

Warning Status Message

Advertising