Advanced Microprocessor Controls Setup

9

Select Options

The following table lists choices on the Select Options menu. These should match the options installed

with your unit and should not need to change during normal operation.

Calibrate Sensors

The temperature and humidity sensors can be calibrated by selecting this menu item. “Sensor” shows

the actual sensor reading or raw reading. “Calibrated” shows the sensor reading after the calibration

offset has been added. The temperature sensor can be calibrated ±5 degrees Fahrenheit and the

humidity sensor can be calibrated ±10% RH. When calibrating the humidity sensor, the value shown

will always be % RH, even though absolute humidity control may be selected. If absolute humidity

control is selected, the Normal Status Display will display the adjusted reading and may not agree

with the relative humidity reading displayed while in calibration.

Show DIP Switches

The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires

opening the upper panel for access to the DIP switches on the microprocessor control board.

These selections should match options installed on your unit and should not need to change during

normal operation. Switches 1 through 6 are self-explanatory. Switch 7 is described in more detail

below. DIP switch 8, not shown above, enables the password feature when set to ON and disables the

password feature if set to OFF.

Table 3

Select options

Option

Selection

Heating

Yes or No

Humidifier

Yes or No

Dehumidifier

Yes or No

Humidifier Pan

Small or Large

Hot Gas Reheat

Yes or No

Heat Stages*

2 or 3

Dehumidification Stages

1 or 2

*If heat stage is set to 2 on a chilled water unit, the
reheat 3 output is energized on a call for dehumidification.

NOTE
Power must be cycled off, then on from the unit disconnect switch for the control system

to update the DIP switch settings (except for switch 8).

Table 4

DIP switch settings

DIP

Switch

Number

OFF

ON

1

DX Compressor Cool

Chilled Water

2

Electric/Hot Gas Reheat

Hot Water Reheat

3

2 Step DX

4 Step DX

4

No GLYCOOL

GLYCOOL

5

No Dual Cooling

Dual Cooling

6

Not Used

Not Used

7

Delayed Reheat

Dehumidification with Normal Reheat