Calibration, 5 communications, Liebert site product device – Emerson Liebert Deluxe System/3 DH User Manual

Page 50: 1 monitor functions, Communications, Monitor functions

Advertising
background image

Response by Control Type—Advanced Microprocessor Controls

42

Calibration

Calibration should not be required for most installations. The accuracy of this display is approxi-

mately 1%.
The display is calibrated by the slope and intercept values of Analog Input #1. The position of the

water is calculated from the analog output of the LT750 using the formula:

position = analog reading/full scale reading X (measured length + slope) + intercept

position is the distance from the LT750 to the position of the detected water.
measured length is the length of the cable which is calculated automatically when the layout is

defined. The units for these values are in floor tiles.
The intercept value read from Analog Input #1 is added to the measured position of a water indication

to determine which tile to highlight. For example, if water is displayed under the seventh tile but

determined to be under the fifth tile, set the offset value to -2 tiles. Use the intercept value to correct

errors close to the start of the cable.
Accuracy errors farther out on the cable should be corrected using Analog Input #1's slope value. This

value effectively adjusts the measured length of the cable. Increasing the effective length of cable will

increase the distance of the water and move the highlighted tile farther along the cable, and vice

versa. Unlike the intercept, which adjusts by the same amount for all locations on the cable, the slope

increases its effect for larger distances.
The best procedure to calibrate the cable would be to first simulate water close to the LT750, about 5

tiles out. Adjust the intercept to get the correct reading. Next, simulate water 5 tiles from the end.

Adjust the slope to get the correct reading.

5.5

Communications

The control system uses a two-wire, RS-422 channel to communicate with remote monitoring systems

via Liebert Site Products. This communication, directly out of the control, uses a proprietary protocol.

Your unit can have a variety of different Site Product devices wired to this port depending on the

monitoring system you are using.

Liebert Site Product Device

• SiteScan Centralized Monitoring System—Stand alone facility monitoring system
• SiteLink BMS Interface Module—For Modbus or BACnet communication to a third party moni-

toring system

• OpenComms Network Interface Card—For Ethernet connection using SNMP protocol
• OpenComms D.O. Interface Card—For discrete outputs of status and alarm conditions
• Mini-Remote - Stand alone individual unit remote monitor
• ECA2 Communication Adapter—For remote service monitoring directly or via a modem

Consult the User Manual of the appropriate device for specific installation and operation information.

5.5.1 Monitor functions:

1. Temperature/Humidity: Present readings
2. Status: Cooling/Heating and Humidifying/Dehumidifying operating status in percent
3. Present Alarms: Alarms presently active
4. Alarm History: 10 most recent alarms (60 most recent alarms for AG)
5. Run Time Log: Operating hours on major components
6. Daily Log: High and Low Temperature & Humidity