3 chilled water systems, Cooling, Heating – Emerson Liebert Deluxe System/3 DH User Manual

Page 10: Humidification, Dehumidification, 4 glycool™ (chilled glycol cooling) systems, 5 dual source cooling systems, Chilled water systems, Glycool, Dual source cooling systems

Advertising
background image

Introduction

2

1.1.3 Chilled Water Systems

These systems utilize a central chiller and control cooling by modulating a control valve in the chilled

water line.

Cooling

Modulating output water valve

Heating

Three stages of electric reheat standard; steam/hot water optional

Humidification

Infrared standard, steam grid and steam generating optional

Dehumidification

Chilled water valve opens proportionally in response to room needs

1.1.4 GLYCOOL

(Chilled Glycol Cooling) Systems

GLYCOOL

systems have all of the features of a compressorized water or glycol system, plus a sec-

ond cooling coil that is connected into the water circuit. When fluid temperature is sufficiently low

(below room temperature), cooling is provided by circulating the fluid through the second cooling coil

(with the flow controlled by a motorized valve). This is then the primary cooling source, greatly reduc-

ing the compressor operation.

Cooling

Modulated cooling valve opens proportionally to match room needs (primary), two or four stages of

mechanical refrigeration (secondary)

Heating

Three stages of electric reheat standard

Humidification

Infrared standard; steam generating optional

Dehumidification

Utilizes the lag compressor

1.1.5 Dual Source Cooling Systems

This system has all the features of a compressorized system but adds a second cooling coil that is con-

nected to a source of chilled water. This second coil is controlled by a modulating control valve. It is

the primary source of cooling and dehumidification so compressor operation is reduced.

Cooling

Second coil opens proportionally in response to the room needs (primary), two or four stages of

mechanical refrigeration (secondary)

Heating

Three stages of electric reheat standard

Humidification

Infrared standard; steam generating optional

Dehumidification

Standard Controls use the lag compressor. Advanced Controls use the chilled water valve and then

the lag compressor if required by the load.