Advanced Microprocessor Controls Setup

7

3.3.5 Analog Sensors

The four (4) analog sensor inputs can be monitored from this submenu of Status/Alarm Data. The

inputs are filtered and displayed along with the text label assigned during setup. See Analog

Setup on page 12.

3.4

Main Menu (AM)—Setpoints/Setup

Selecting Setpoints/Setup from the Main Menu will display the following selections:

VIEW SETPOINTS
SETUP SYSTEM
RUN DIAGNOSTICS
CHANGE PASSWORDS

3.4.1 View Setpoints Selection

Control and alarm setpoints can be reviewed or changed with this submenu of Setpoints/Setup. The

following table lists the default setpoints and their allowable ranges.

3.4.2 Setup System Selection

The Setup System, a submenu of Setpoints/Setup, includes the following selections:

SETUP OPERATION
SELECT OPTIONS
CALIBRATE SENSORS
SHOW DIP SWITCHES
SELECT CONTROL TYPE
SETUP ALARMS
HUM CONTROL METHOD
ANALOG SETUP
SET STATUS DISPLAY
CALIBRATE ACTUATOR

NOTE
Setpoints and system setup parameters are kept in nonvolatile memory.

Table 1

Default control and alarm setpoints

Setpoint

Default

Range

Temperature Setpoint

72°F

40 to 90°F (5 to 32°C)

Temperature Sensitivity

2.0°F

1 to 9.9°F (0.6 to 5.6°C)

Humidity Setpoint

50%

20 to 80% RH

Humidity Sensitivity

5%

1 to 30% RH

High Temperature Alarm

80°F

35 to 95°F (2 to 35°C)

Low Temperature Alarm

65°F

35 to 95°F (2 to 35°C)

High Humidity Alarm

60%

15 to 85% RH

Low Humidity Alarm

40%

15 to 85% RH

Advertising