Advanced Microprocessor with Graphics Control Setup

23

4.5

Main Menu (AG)—Operating Status

The Operating Status is intended to provide the user with displayed information concerning what the

control is calling for the system to do.

For example: The display indicates the chilled water valve is 68% open. On a new call for cooling, it

takes several seconds for the valve to travel from full closed to 68% open. So when the display reads

68%, it may take a few seconds for the valve to actually open 68%. Also, if the display indicates a com-

pressor is operating but the compressor has not turned on yet, it may be off because of the short cycle

control (see 5.3.1 - Short Cycle Control).

4.6

Main Menu (AG)—View/Set Control Setpoints

Control setpoints can be reviewed and/or changed through the display. The following table lists the

default setpoints and their allowable ranges.

*Unit will operate at these conditions but will not control to these extremes of conditions.

4.7

Main Menu (AG)—Setup System

Selecting SETUP SYSTEM will step to the following menu:

• SETUP OPERATION
• SELECT OPTIONS
• CALIBRATE SENSORS
• CALIBRATE VALVE ACTUATOR
• SELECT CONTROL ALGORITHM
• SELECT HUMIDITY SENSING MODE
• SET STATUS DISPLAY
• CHANGE PASSWORDS

NOTE
There may be some time lapse before a specific component matches the displayed number.

Table 8

Default control and alarm setpoints

Setpoint

Default

Range*

Temperature Setpoint

72°F

40 to 90°F (5 to 32°C)

Temperature Sensitivity

2.0°F

1 to 9.9°F (0.6 to 5.6°C)

Humidity Setpoint

50%

20 to 80% RH

Humidity Sensitivity

5%

1 to 30% RH

High Temperature Alarm

80°F

35 to 95°F (2 to 35°C)

Low Temperature Alarm

65°F

35 to 95°F (2 to 35°C)

High Humidity Alarm

60%

15 to 85% RH

Low Humidity Alarm

40%

15 to 85% RH