2 select options, Table 10 select options, 3 calibrate sensors – Emerson Liebert Deluxe System/3 DH User Manual

Page 33: 4 calibrate valve actuator, 5 select control algorithm, Select options, Calibrate sensors, Calibrate valve actuator, Select control algorithm, Table 10

Advertising
background image

Advanced Microprocessor with Graphics Control Setup

25

4.7.2 Select Options

The following table is a list of features that should match the options installed with your unit and

should not need to change during normal operation.

4.7.3 Calibrate Sensors

The temperature and humidity sensors can be calibrated by selecting this menu item. “SENSOR”

shows the actual sensor reading or raw reading. “CALIBRATED” shows the sensor reading after the

calibration offset has been added. The temperature sensor can be calibrated ±5 degrees Fahrenheit

and the humidity sensor can be calibrated ±10% RH. When calibrating the humidity sensor, the value

shown will always be % RH, even though absolute humidity control may be selected. If absolute

humidity control is selected, the Normal Status Display will display the adjusted reading and may

not agree with the relative humidity reading displayed while in calibration.

4.7.4 Calibrate Valve Actuator

For systems that use a valve actuator for chilled water or glycol cooling, the actuator timing may be

calibrated or adjusted through this feature. This is the time it takes for the valve to travel from full

closed to full open. It is programmable from 0 to 255 seconds. The factory default time is 165 seconds

and should not be changed unless the actual valve travel time is not correct. The full valve travel time

is used by the control to determine the appropriate valve position. For example, if the valve travel

time is 165 seconds and 50% cooling is being called for, the valve will open for 83 seconds to achieve

50% open. To change the valve travel time, first enter the “CALIBRATE VALVE ACTUATOR” screen.

The display will show the present period used by the control for valve actuator full travel. Press

ENTER and adjust the time using the UP/DOWN arrows. When the correct time is displayed, press

ENTER to store the new time in memory.

4.7.5 Select Control Algorithm

The type of system control method used by the microprocessor can be selected from the front panel.

The default setting is INTELLIGENT, which approximates the actions that a human operator would

take to maintain precise, stable control. The control logic uses Artificial Intelligence techniques

including “fuzzy logic” and “expert systems” methods to maintain precise, stable control and increase

reliability by reducing component cycles. PROPORTIONAL is a standard control method that uses

one gain factor (temperature sensitivity adjustment). TUNABLE PID (Proportional, Integral, and

Derivative) uses three gain factors selected by the operator. PID allows precision tuning, but requires

an experienced operator and seasonal adjustments. Note that if PID is selected, it is used for temper-

ature control while humidity will continue to use Proportional Control. For chilled water units with

the optional Variable Speed Drive, Intelligent is required for proper operation. Refer to 5.0 -

Response by Control Type—Advanced Microprocessor Controls for more details on types of

control.

Table 10

Select options

Option

Selection

Heating

Yes or No

Humidifier

Yes or No

Dehumidifier

Yes or No

Humidifier Pan

Small or Large

Hot Gas Reheat

Yes or No

Heat Stages*

2 or 3

Dehumidification Stages

1 or 2

*If heat stage is set to 2 on a chilled water unit, the
reheat 3 output is energized on a call for
dehumidification.