4.8.4 DIP Switches

The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires

opening the front panel for access to the DIP switches on the microprocessor control board.

These selections should match options installed on your unit and should not need to change during

normal operation. Switches 1 through 7 are self explanatory. DIP switch 8, not shown in the table,

enables the password feature when set to ON and disables the password feature if set to OFF.

Dehumidification with Normal or Delayed Reheat

Dehumidification with normal reheat allows for operating both compressors and reheats simulta-

neously. It is very important that electrical service to the unit be sized and wired for this option if

selected.

With delayed reheat selected, the reheats are prevented from turning on when dehumidifying with

both compressors until the point at which 100% heating is called for. At this time, the compressors

are turned off until the reheats bring the temperature back up to the point at which the reheats are

turned off.

4.9

Main Menu (AG)—Date and Time

The current date and time is available through the display. This feature allows the date and time to

be read or changed and is accessed by selecting “DATE AND TIME” from the Main Menu. The “DATE

AND TIME” is used by the control for recording the Alarm History and plotting graphs.

The date and time are backed up by a battery.

4.10 Main Menu (AG)—Plot Graphs

Selecting Plot Graphs will step to the following menu:

• TEMPERATURE PLOT
• HUMIDITY PLOT
• ANALOG SENSOR #1 PLOT
• ANALOG SENSOR #2 PLOT
• ANALOG SENSOR #3 PLOT
• ANALOG SENSOR #4 PLOT
• MODIFY PLOT SCALES

NOTE
Power MUST be cycled off, then on from the unit disconnect switch for the control system to

update the DIP switch settings (except for switch 8).

Table 11

DIP switch settings

Number

OFF

ON

1

Compressor Cool

Chilled Water

2

Electric/Hot Gas Reheat

Hot Water Reheat

3

2 Step

4 Step

4

No GLYCOOL

GLYCOOL

5

No Dual Cooling

Dual Cooling

6

Not Used

Not Used

7

Delayed Reheat

Dehumidification with Normal Reheat

!

CAUTION

The result of electrical service to the unit not being sized properly for this option could be

nuisance trips of the building circuit breakers (or fuses) or, in extreme cases, damage to

building wiring.