7 air cooled condenser, Figure 8 outdoor fan/condenser configuration, Air cooled condenser – Emerson Liebert Deluxe System/3 DH User Manual

Page 62: Figure 8, Outdoor fan/condenser configuration

Advertising
background image

Component Operation and Maintenance, Checks and Adjustments

54

7.4.7 Air Cooled Condenser

Restricted airflow through the condenser coil will reduce the operating efficiency of the unit and can

result in high compressor head pressure and loss of cooling.
Clean the condenser coil of all debris that will inhibit air flow. This can be done with compressed air

or commercial coil cleaner. Check for bent or damaged coil fins and repair as necessary. In winter, do

not permit snow to accumulate around the sides or underneath the condenser.
Check all refrigerant lines and capillaries for vibration isolation. Support as necessary. Visually

inspect all refrigerant lines for signs of oil leaks.

Checking Refrigerant Charge (Lee–Temp™/ Flood Back Head Pressure Control)

The system refrigerant level must be periodically checked. This is easily done by the following proce-

dure:
1. Adjust temperature setpoint in the unit so that the compressor will run continuously.
2. The refrigerant level is visible through two sight glasses on the receiver, and will vary with

ambient temperature.
a. 40°F (4.4°C) and lower – Midway on the bottom sight glass.
b. 40 to 60°F (4.4 to 15.6°C) – Bottom sight glass should be clear with liquid.
c. 60°F (15.6°C) and above – Midway on the top sight glass.

3. Return temperature setpoint to desired number.

Figure 8

Outdoor fan/condenser configuration

Fan Motor M1

Inverted Traps

by Others

Hot Gas Line

Lee-Temp Heater Pad

Connection Boxes

Electric Service

Supplied by Others

Electric Service

Supplied by Others

Hot Gas Line

Inverted Traps

by Others

Fan Motor FS

Secure each leg to

condenser frame at all

points shown using

hardware provided

Liquid Line

Liquid Line

Advertising
This manual is related to the following products: