7.4.9 Compressor Replacement

Infrequently, a fault in the motor insulation may result in a motor burn. However, in a properly

installed system, burnouts rarely occur. Of those that do, most are the effects of mechanical or lubri-

cation failures, resulting in the burnout as a secondary consequence.
If problems that can cause compressor failures are detected and corrected early, a large percentage

can be prevented. Periodic maintenance inspections by alert service personnel on the lookout for

abnormal operation can be a major factor in reducing maintenance costs. It is easier and far less

costly to take the steps necessary to ensure proper system operation than it is to allow a compressor

to fail and require replacement.
When troubleshooting a compressor, check all electrical components for proper operation.
1. Check all fuses and circuit breakers.
2. Check Hi-Lo Pressure switch operation.
3. If a compressor failure has occurred, determine whether it is an electrical or mechanical failure.

Mechanical Failure

A mechanical compressor failure will not be indicated by a burned odor. The motor will attempt to

run. If you have determined that a mechanical failure has occurred, the compressor must be replaced.
If a burnout does occur, correct the problem that caused the burnout and clean the system. It is impor-

tant to note that successive burnouts of the same system are usually caused by improper cleaning.

Electrical Failure

An electrical failure will be indicated by a distinct pungent odor. If a severe burnout has occurred, the

oil will be black and acidic.
In the event that there is an electrical failure and a complete burnout of the refrigeration compressor

motor, the proper procedures must be performed in order to clean the system to remove any acids that

would cause a future failure.

There are two kits that can be used with a complete compressor burnout - Sporlan System Cleaner

and Alco Dri-Kleener. Follow the manufacturer's procedure.

!

CAUTION

Avoid touching or contacting the gas and oils with exposed skin. Severe burns will result. Use

long rubber gloves in handling contaminated parts.

NOTE
Damage to a replacement compressor caused by improper system cleaning constitutes abuse

under the terms of the warranty, and the WARRANTY WILL BE VOID.