Component Operation and Maintenance, Checks and Adjustments

63

Figure 12 Steam generating humidifier control board

7.6

Electric Reheat

Table 20

DIP switch settings for steam generating humidifier

Unit Rated

Voltage

Capacity

SW1

SW2

SW3

SW4

Rated Values

Voltage

AMP Set Pt

200/208

11

Off

On

Off

On

208

12.6

200/208

22

On

Off

On

On

208

23.8

230

11

Off

Off

Off

On

240

10.5

230

22

Off

Off

On

On

240

20.3

380/400/415

11

On

On

Off

Off

400

6.3

380/400/415

22

Off

On

On

On

400

12.6

460

11

On

Off

Off

Off

480

5.5

460

22

Off

Off

Off

On

480

10.5

575*

11

Off

Off

Off

Off

575

4.2

575*

22

Off

On

Off

On

575

9.8

*The values are only suitable in models FH600C and FH740C. All other models use a 575 volt to 460 volt step-down
transformer and therefore use the 460V settings.

!

CAUTION

Reheat element sheaths and fins are manufactured with stainless steel. Regular inspections

are necessary to assure proper cleanliness of the reheating element. Should inspection reveal

corrosion particles on the reheating element or adjoining surfaces (including ducts and

plenums), appropriate cleaning should be performed. Periodic reheating element replacement

may be required to meet specific application requirements.