0 troubleshooting, Table 21 blower troubleshooting, Table 22 chilled water troubleshooting – Emerson Liebert Deluxe System/3 DH User Manual

Page 72: Roubleshooting, Table 21, Blower troubleshooting, Table 22, Chilled water troubleshooting, Warning, Caution

Advertising
background image

Troubleshooting

64

8.0

T

ROUBLESHOOTING

Use this section in troubleshooting your unit. Also refer to 6.0 - Alarm Descriptions and Solu-

tions. Suggestions are grouped by product function for convenience.

!

WARNING

Only qualified personnel should perform service on these units. Lethal voltage is present in

some circuits. Use caution when troubleshooting with power on. Disconnect and lock out

power before replacing components. Use caution and standard procedures when working with

pressurized pipes and tubes.

!

CAUTION

When using jumpers for troubleshooting, always remove jumpers when maintenance is

complete. Jumpers left connected could override controls and cause equipment damage.

Table 21

Blower troubleshooting

Symptom

Possible Cause

Check or Remedy

Blower will not start

No main power

Check L1, L2 and L3 for rated voltage.

Blown fuse or tripped circuit

breaker (CB)

Check fuses or CBs to main fan.

Overloads tripped

Push reset button on main fan overload. Check amp. draw.

No output voltage from

transformer

Check for 24 VAC between P24-2 and P24-1. If no voltage,

check primary voltage.

Control fuse blown or circuit

breaker tripped

Check for 24 VAC between P4-4 and E1. If no voltage,

check for short. Replace fuse or reset circuit breaker.

Start switch SS not making

contact (SM only)

Jumper P9-1 to P9-2. Unit should start. If unit stops after

jumper is removed, replace S1.

Blower runs but controls

will not operate

Relay R1 not making contact

(standard controls only)

Check for 24 VAC between P36-9 and P36-10. If voltage is

not present, R1 is not receiving power.
Check air switch. Jumper P36-4 to P36-7 If R1 closes, air

switch is not closing (check for blower rotation, loose wiring,

and pinched tubing.) Remove jumper.
Check for 24 VAC at R1 coil. If the voltage is present and R1

is not pulling, replace R1.

Table 22

Chilled water troubleshooting

Symptom

Possible Causes

Check or Remedy

Actuator Motors

No 24 VAC power to motor

Check for 24 VAC between P22-3 and P22-5 (open), or P22-

1 and P22-5 (closed).

Chilled water or hot

water/steam valve not

opening

Motor operates but valve won’t

open

Check linkage for adjustment and be sure that it is tight on

the valve.

Modulating Motors

No 24 VAC power to motor

Check linkage for adjustment and be sure that it is tight on

the valve.

No signal from control

Check DC voltage on printed circuit board in motor. Terminal

No. 1 is grounded and No. 3 is positive. DC voltage should

vary from 0.8 to 2.0 VDC or above as temperature control is

varied below room temperature on cooling valve or above

room temperature on heating valve.

Motor not working

Remove wires on terminal No. 1 and No. 3 from the motor

(do not short). With 24 VAC power from TR to TR jumper

terminal 1 and 2 on motor to drive open. Remove jumper to

drive closed, if motor fails to work, replace it.

Advertising
This manual is related to the following products: