Table 23 – Emerson Liebert Deluxe System/3 DH User Manual

Page 73

Advertising
background image

Troubleshooting

65

Table 23

Compressor and refrigeration system troubleshooting

Symptom

Possible Cause

Check or Remedy

Compressor will not

start

Power off

Check main switch, fuses or CBs and wiring

Current overload open

Reset manually

Loose electrical connections

Tighten connections

Compressor motor burned out

Check and replace compressor if defective.

Compressor will not

operate, contactor not

pulling in

No call for cooling

Check monitor status.

Solenoid valve not energizing

Hold screwdriver over solenoid and check for magnetic field.

This indicates solenoid is energized.

Low pressure switch not making

contact

Check gas pressure - manually energize low pressure

switch.

Compressor will not

operate, contact not

pulling in

High pressure switch open

Reset switch. Refer to other refrigeration troubleshooting

suggestions.

Compressor contactor

pulled in but

compressor will not

operate

Blown fuse or tripped CB

Check for line voltage after fuses or CBs, and after

contactors.

Compressor runs for

three minutes then

stops; contactor drops

out. Motor operates but

valve won't open

Low pressure switch not closing

Check for low gas pressure. Compressor is running on

Positive Start Kit (air cooled systems only).

Solenoid not opening

Check magnetic field to see if energized.

High discharge

pressure

Dirty condenser or drycooler fins

Clean coil

Condenser equipment not

operating

Check operation.

High refrigerant charge

Check refrigerant charge.

Hot gas bypass valve adjusted

improperly

Adjust properly.

Water regulating valve adjusted

improperly

Adjust properly.

Low discharge pressure

Excessive water now through

condenser

Adjust water regulating valve

Suction service valve partially

closed

Open the valve.

Leaky compressor suction valves

Pump down, remove the cylinder head, examine valves and

valve seats; replace if necessary

Worn piston rings

Replace compressor.

Faulty head pressure control

valve or condenser fan speed

control

Replace if defective.

Low suction pressure

Insufficient refrigerant in system

Check for leaks, repair, and add refrigerant

Dirty air filters

Change filters.

Plugged filter-drier

Replace filter.

Improper superheat adjustment

Reset expansion valve for 10-15°F

Defective expansion valve

sensing element

Replace element

Poor air distribution

Check duct work for closed dampers. Check for underfloor

restrictions at or near the unit.

Low condensing pressure

Check head pressure control device.

Slipping belts

Inspect and adjust