Table 24 dehumidification troubleshooting, Table 25 glycol pumps troubleshooting, Table 24 – Emerson Liebert Deluxe System/3 DH User Manual

Page 75: Dehumidification troubleshooting, Table 25, Glycol pumps troubleshooting

Advertising
background image

Troubleshooting

67

Compressor continually

cycles

Faulty low pressure switch

Repair or replace.

Dirt or restriction in tubing to

pressure stat

Check and clean tubing.

Defective liquid line solenoid

valve

Check valve and solenoid operator; replace if necessary.

Plugged filter-dryer

Replace filter

Compressor motor

protectors tripping or

cycling

High discharge pressure

Check for loss of condenser water or blocked condenser fan

or coil.

Defective overload relay

Replace.

High suction temperature

Reduce suction temperature by expansion valve adjustment

or provide desuperheating.

Loose power or control circuit

wiring connection

Check all power and control circuit connections.

Defective motor

Check for motor ground or short. Replace compressor, if

either condition is found.

Compressor cycles on

locked rotor

Low line voltage

Check line voltage and determine location of voltage drop.

Seized compressor (remove

bearing head assembly and

attempt to rotate crankshaft)

Replace compressor.

Compressor motor defective

Check for motor winding short or ground.

Single phasing

Check voltage across all 3 legs at contactor. Correct source

problem.

Liquid refrigerant condensing in

cylinder

Check and replace valve plates.

Motor burnout

Check control panel for welded

contactor contacts or welded

overload contacts

Replace defective components.

Table 24

Dehumidification troubleshooting

Symptom

Possible Cause

Check or Remedy

No dehumidification

Control not calling for

dehumidification

Check monitor status.

Compressor contactor not pulling in

See Compressor Section.

Compressor won't run; fuse blown

or CB tripped

See Compressor Section. Check fuses or CBs and

contacts. Check line voltage

Table 25

Glycol pumps troubleshooting

Symptom

Possible Cause

Check or Remedy

Suddenly stops

pumping

Clogged strainer or impeller

Clean out debris.

Suddenly slow pumping

Clogged impeller, diffuser, or line

Clean out debris and use strainer.

Excessive leakage

around the pump shaft

while operating

Worn seal or packing

Replace seal or packing.

Performance poor

Worn impeller or seal

Replace with new impeller or seal.

Suction lift too high

Relocate pump closer to supply.

Motor not up to speed; low voltage

Larger lead wires may be required Check for proper

line voltage (±10%).

Worn bearings

Replace pump

Noisy operation

Worn motor bearings

Replace pump

Low discharge head

Throttle discharge-improve suction conditions.

Debris lodged in impeller

Remove cover and clean out.

Cavitating pumps

Adjust system pressures.

Table 23

Compressor and refrigeration system troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy