Table 27 humidifier-infrared troubleshooting, Table 28 reheat troubleshooting, Table 27 – Emerson Liebert Deluxe System/3 DH User Manual

Page 77: Humidifier—infrared troubleshooting, Table 28, Reheat troubleshooting

Advertising
background image

Troubleshooting

69

Excessive arcing in the

canister

Drain valve clogged or defective

Verify that drain valve operates freely when activated.

Clean valve and replace coil or valve if defective.

Flush canister several times and replace if arcing

persists

Improper water supply

If water is commercially softened, reconnect humidifier

to raw water supply, drain canister, and restart If

connected to hot supply, reconnect to cold water.

Insufficient drain rate

Increase drain rate by adjusting % pot on circuit board

above the preset 87% (85%) to roughly 92% (90%).

Excessive iron content in water

Analyze iron cement of water. If it exceeds 0.1 mg/l,

install a filter to remove iron from water supply.

On cold start-up,

canister fills, high water

alarm activates and

humidifier fails to reach

full amperage after 24

hours

Conductivity of water too low

Turn the % pot to roughly 82% (80%). Restart

humidifier. If canister fails to reach FLA in 24 hours,

have water supply conductivity checked.

Fill solenoid not closing tightly

If humidifier returns to canister full condition, verity that

the fill solenoid closes tightly.

Table 27

Humidifier—infrared troubleshooting

Symptom

Possible Cause

Check or Remedy

No humidification

Humidifier pan not filling

Check water supply.
Check fill valve operation
Check drain stand pipe adjustment
Check for clogged waterline

Control not calling for humidity

Check monitor status

Humidity contact not pulling in

Check visually. If contact is made, check line voltage

after contactor and fuses or CBs.
Check for open humidifier safety stat. Jumper between

terminals P35-6 and P35-15. If contactor pulls in,

replace safety. Remove jumper.

Humidifier bulb burned out

Replace bulb. Loosen lead on old bulb. Trim excess

lead length on new bulb to avoid shorts.

Table 28

Reheat troubleshooting

Symptom

Possible Cause

Check or Remedy

Reheat will not operate;

contactor not pulling in

Control not calling for heat

Check monitor status.

Reheat safety stat open

Jumper between terminals P34-1 and P34-2. If reheat

operates, safety is open. Remove jumper. Replace

safety.

Reheat not operating,

contactor pulling in

Heater burned out

Turn off power and check heater continuity with Ohm

meter.

Table 26

Humidifier—steam generator troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy