PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

85

Date and Time Setup Menu (SETTIME)

The year, month, day, hour, and minute may all be set by the user. The real time clock will need to be
reset if external power and battery power are lost.
To program the time, select the time or date component to be programmed, and press Enter. To enter
the time or date as a numeric value, see Setting Numeric Values on page 24 for more information.
Changing the time (hours and minutes) will reset the second clock to 0.

Data Log Setup (DATALOG)

The Data Log menu is used to setup and enable the data log functions. The scanner may contain up to
511 records, each containing the date, time, and log number. Each record may hold either the first eight
enabled Modbus PVs and any enabled math channel CVs; or the rate, total and grand total.
The data log can hold 511 records of the first eight enabled Modbus PVs and math channel CVs; 511
records containing the rate, total, and grand total; or 256 records of each.
The data log will make a record of the first eight enabled Modbus PVs and math channel CVs if any
Modbus or math channels are enabled. The data log will make a record of the rate, total, and grand total if
any of these parameters is enabled. The frequency of these records depends on the data log settings.
For example: If the pulse input is disabled, PV 1, 2, 3, and 4 are enabled, and CV 1 and 2 are enabled,
the data log may record 511 logs containing PV 1, 2, 3, and 4, as well as CV 1 and 2. The data log will
record these values even if CV2 is the only value set to display.
If the pulse input is enabled, the data log will record 256 logs containing PV 1, 2, 3, and 4, and CV 1 and
2. It will also record 256 logs containing the rate, total, and grand total.