PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

9

INPUT POWER

9-30 VDC, 38mA max. 2.2 W.

DATA LOGGING

Up to 511 records, recorded 4/day at specific times or at defined time intervals.
Record contains first eight enabled Modbus PVs; C1-4 if enabled; date; time;
pulse rate, total, and grand total with units; and log number.

ISOLATION

All Models:

500 V opto-isolated pulse input-to-power/OC output with
isolated input enabled.
500 V input/power-to-RS-485 serial communications

-AXA Models:

500 V input/power-to-analog output

ENVIRONMENTAL

Operating temperature range: -40 to 75°C
Storage temperature range: -40 to 75°C
Backlight deactivated below temperatures ≈ -20°C
Relative humidity: 0 to 90% non-condensing

NON-VOLATILE
MEMORY

All programmed settings and total reading are stored in non-volatile memory for a
minimum of ten years if power is lost.

CONNECTIONS

Screw terminals accept 12 to 22 AWG wire

ENCLOSURE

Injection-molded plastic with clear polycarbonate window, color: gray. NEMA 4X,
IP65. Material: polycarbonate with UV stabilizer. Default conduit connections:
Three ¾" NPT threaded conduit openings. Two ¾" NPT plastic plugs installed.

MOUNTING

May be mounted directly to conduit. Two slotted flanges for wall mounting or NPS
1½" to 2½" or DN 40 to 65 mm pipe mounting. See Mounting Dimensions on
page 97.

DISPLAY
ORIENTATION

Display may be mounted at 90° increments up to 270° from default orientation.

OVERALL
DIMENSIONS

5.67" x 5.25" x 4.18" (W x H x D)
(144 mm x 133 mm x 106 mm)

WEIGHT

1.65 lbs (26.4 oz, 0.75 kg)

WARRANTY

3 years parts and labor

Modbus Operating Modes

MASTER

Processes and displays data read from Modbus RTU slave devices. Up to 16
process variables (PVs) from up to 16 slave devices. Each PV programmed
individually.

SLAVE

Processes data sent to it from a Modbus RTU master device.
Note: Refer to Modbus Register Tables at www.predig.com for details.

SNOOPER

Listens to the Modbus traffic and picks up a specific register or registers being
polled by a Master device from a specific slave device and processes the data
being read. Up to 16 process variables (PVs) from up to 16 devices. If multiple
registers are polled by the master with one command, only the first returned
value will be read.

MASTER POLL TIME

0.1 to 99.9 sec. Time between read-commands.

MASTER TIMEOUT

0.1 to 99.9 seconds. Time elapsed after a poll request is made before the
scanner considers that request to have failed.

NUMBER OF RETRIES 1-99. The number of retries the scanner will make when requesting data before

reporting an error condition on the PV.

SNOOPER
RESPONSE TIME

0.1 to 99.9 seconds. Time since the last PV update the before being
considered an error.

SLAVE TIMEOUT

0.0 to 99.9 seconds. Time elapsed after the last data received from a master
before the scanner considers the data to be out of date. Programming 0
disables the timeout, and PV data will be displayed indefinitely despite not
being updated regularly.