Introduction, Main features, Installation – RISCO Group Lumin8 User Manual

Page 4

Advertising
background image

LuMIN8 Installation Instructions

4

Introduction

RISCO Group’s LuMIN8 External Sounder combines high performance and reliability with an exclusive
design, making it the perfect finishing touch for your security installations.
LuMIN8 can be connected to any alarm system, or it can be installed on serial BUS of RISCO Group’s
ProSYS FreeCom Integrated Security System or GT series Control Panels.
When installed in BUS serial mode the LuMIN8 supports remote parameter setting and remote
diagnostics, saving time and money on installation and maintenance and reducing repeat site visits.

The LuMIN8 uses a patent pending spotlight and long life SLT strobe.

Main Features

Patent pending spotlight lamp to illuminate
your logo

Long life SLT strobe (patent pending)

UV-treated vandal proof polycarbonate
housing

Double skin with internal metal cover
(optional)

SAB/SCB selectable

Auto recharging battery circuit

Double tamper protection (Wall & Cover)

Remote and local engineer mode

Flexible strobe activation when connected in
serial mode

Remote diagnostics and control when
connected in serial mode

Protection from power supply inverted
connection

Audible confirmation of set/unset

Installation

Warning:

The circuit board contained within the encapsulated module produces high voltages that may be present at the piezo
head connections.

1. Open the screw cover located at the bottom of the sounder and unscrew the cover screw.
2. Open the terminal block cover.
3. Use the back plate of the sounder as a template and mark the position for fixing the sounder.
4. Drill the holes and insert wall plugs.
5. Pull the connection cables through the back plate of the sounder.
6. Screw the back plate of the sounder firmly to the mounting surface. Use three 2" No 10 screws
7. Configure the dipswitches as required.
8. Make the required connections to the terminal block.
9. Connect the battery for the backup power supply.

Note:

The sounder will sound for 4 seconds when the battery is connected.

10. If required install the lamp spotlight (see page 14).
11. Close the terminal block cover, close the cover and tighten the screw.

Recommended maximum cable distances (single sounder)

Cable Type

No of Cores

Distance SAB

Distance SCB

4 Core 7/0.2

1 x 0V ; 1 x 12V

35m(1PZ) / 25m(2PZ)

100m

6 Core 7/0.2

2 x 0V ; 2 x 12V

71m(1PZ) / 50m(2PZ)

300m

Note: (Health and Safety Advice)

The LuMIN8 sounders covered by this manual are capable of producing high volume sound. It is essential that suitable
ear protection is worn when installing or testing the sounder.

Note:

For installation of the metal shroud follow the instructions attached with the product.