5.2

Multiple Zones, one fan per zone:

Testing multiple zones can require one fan on each separate zone. These zones can be adjacent rooms
or separate floors.

Problem 2: Uneven building test pressures between zones can be caused by a Common set point
control as shown in Figure 14. The same control signal can create uneven pressures in unconnected
zones. This happens when one zone is leakier than the other.

Figure 14: Problem2: Uneven pressures between zones caused by Common set point control

Solution 2: Use Individual set point control (“Individual Control” turned On).

Eliminate the problem of being unable to reach the same pressure in separate zones by controlling each
fan individually with its own gauge. The solution is depicted in Figure 15.
To perform this with FanTestic, click Tools →Advanced Options → Settings tab → check “Individual

Control”

Figure 15: Solution2: Keep pressures even between zones with Individual set point control

50 Pa

60 Pa

50 Pa

50 Pa

Target pressure: 50 Pa

Target pressure: 50 Pa