Retrotec DucTester with DM-2 User Manual

Page 2

Advertising
background image

Step 1:

Prepare ducts and house

Seal all supply and return grills/registers, including

any exterior air inlets, with Grill Mask or tape.

Open all interior doors leading to rooms containing

a supply or return register, and open an exterior door

or window.

Shut off all HVAC (exhaust fans, dryers, A/C, furnaces).

Page 2 of 8

Step 2:

Connect to ducts

Turn off air-handler

and remove all filters.

Tape Flange to main

return or air handler

cabinet using

masking tape.

Attach Flex Duct to

Flange.

Install Mid-Range Ring to start,

as most systems can be tested

on this Range Configuration.

Press [Range Config] to select

range on gauge to match fan,

whenever Range Ring is changed.

Press [Auto Zero] until “On” appears -

to keep the gauge

zeroed and ready

to measure.

Press [Time Avg] until “4s” appears.

Press [Device] until “Retrotec DU200”

appears.

If desired Device does not appear, see:

QuickGuide DM-2 mark II Digital Gauge,
Add/Remove Devices section

Press [Range Config] until

“Mid” appears.

Press [Mode] to cycle through results.

Select based on “Get the results you

need” on page 4.

If you can’t find the required results, see:
QuickGuide DM-2 mark II Digital Gauge

Prepare the DM-2 gauge

Next, prepare the ducts, house, and fan following

Steps 1 through 3.

Mid

Low

Open

Remove Range Rings for

leakier ducts, add Rings

for tighter ducts.