Get the results you need, Show results as leakage area, Step 5: desired results not achieved – Retrotec DucTester with DM-2 User Manual

Page 4: Hold display and jog speed

Advertising
background image

Flow at the induced pressure is the
simplest result.

Mode = “Flow”

Units = “CFM”

Flow per ft

2

(sq ft) is required in some

states, such as WA.

Mode = “Flow/Area”

Units = “CFM/ft

2

(enter a value for Area)

Flow per 100 ft

2

is required for the

following states:

Mode = “Flow/Area”

Units = “CFM/100 ft

2

(enter a value for Area)

Flow reads “TOO LOW” or “----” at test pressure?
If the test pressure has been reached, but

“TOO LOW” or “----” appears, the fan is running too

slowly to measure flow.

Add the next Low-Range Ring.

Change [Range Config] on the DM-2 to match.

Re-adjust speed.

Cannot achieve test pressure at full speed?
If fan reaches 100% speed before reaching the target

pressure:

Remove a Range Ring and try again.

Change [Range Config] on the DM-2 to match.

Check seals on all registers. Look for disconnected

ducts or ducts open to outdoors.

Press [@ Pressure] to get the gauge to calculate

what the flow would be at exactly 25 Pa.

Page 4 of 8

Get the results you need

Press [Mode] until required results appear

Show results as leakage area

Equivalent Leakage Area (EqLA) describes the leakage

area in terms of one large hole in a flat surface.

Press [Mode] until “EqLA” appears.

“PrA” displays the duct pressure and “EqLA” shows

the combined size of all the holes in the ducts.

Step 5:

Desired results not achieved?

620 CFM is the flow rate that would occur at 25 Pa,

even though only 22 Pa was achieved.

CT

DC

DE

GA

ID

IL

IA

ME

MD

MA

NH

NJ

NY

NC

PA

RI

TX

VT

Use “Jog” to activate arrow keys

[

] [

]

then adjust target speed or pressure.

Use “Hold” to freeze results display

and hold fan speed.

Press [Jog/Hold] until “Hold” appears in top center

of display.

Press [Jog/Hold] again to cancel “Hold”.

Press [Jog/Hold] until “Jog” appears.

The [

] [

] keys now adjust the speed just like a

TV remote. With [Set Speed] the % speed

changes. With [Set Pressure] the pressure changes.

Hold display and Jog speed

Leakage area is not a required result, but is a nice

way to visualize the size of the hole in the ducts.

Press [Enter] numbers

[Enter] to

input the floor area if CFM/ft

2

or

CFM/100 ft

2

is used.

*Floor area of 2000 square feet

was entered in the above examples.

[Enter] [2000] [Enter]

“Jog” is only available when [Set Pressure] or

[Set Speed] have a value entered.

The display will be frozen with the current values.

Press [Setup] for menu to change result units

Press [

] to find “Mode Setup”, then [Enter]

Press [

] until the Mode you want is highlighted

Press [Enter] to change displayed result units

Press [Exit] twice to return to main menu

Advertising