Retrotec DU200 DucTester Testing Procedures to meet EnergyStar Standards User Manual

Page 3

Advertising
background image

Page 3 of 4

4.3

Envelope leakage test to meet ENERGY STAR standards


1. Remove Grill Mask and DucTester.
2. Connect the Door Fan to blow outdoors.
3. On the DM-2:

a. Press [Mode] until “Air Chg”

appears.

If unavailable, see Page 4.

b. Press [Device] to get “Retrotec 1000”.

c.

Press [Range Config] to get "B".

4. Press [Enter

Volume

], enter volume in

cubic feet, then press [Enter] to lock in
the volume for each house.

5. Press [Set Pressure] [50] [Enter].
6. Press the [@] key until “@50 Pa” is

displayed.

7. Record the envelope leakage in air

changes at 50 Pa.






Total building
leakage under
depressurization is
the most common
test direction for
residential testing.



Connect green
tube on some
models.