2.5 Enter performance criteria

2.5.1 Case of “Descending interface” as discharge model

“Enclosure pressure limit”

Enter the pressure limit for the enclosure. Any peak pressure higher than this value is
expected to result in structural damage.

“Protected height”

Enter the protected height (the highest level of combustibles). This height is usually
measured to the top of the equipment you are trying to protect.

“Specified hold time”

The required Hold time for a passing test, also known as the “hold time”.

2.5.2 Case of “Continuous mixing” as discharge model

“Enclosure pressure limit”

Enter the pressure limit for the enclosure. Any peak pressure higher than this value is
expected to result in structural damage.

“Minimum concentration”

The final concentration in the enclosure at the end of the hold time

“Specified hold time”

The required Hold time for a passing test, also known as the “hold time”.

3 Calculate the maximum enclosure leakage to maintain the

specified hold time

Click the “Calculate” button once all the data is entered in order to view the results; gray boxes show
the calculated results and are not editable.