FUNCTION

DESCRIPTION

DEFAULT

POSSIBLE CONFIGURATIONS

Bypass voltage

thresholds

Selects the permitted
voltage range for switching
to the bypass

Low: 180V
High: 264V

 Low: 180 - 200 in 1V steps

 High: 250 - 264 in 1V steps

Bypass voltage
threshold for ECO

Selects the permitted
voltage range for operation
in ECO mode

Low: 200V
High: 253V

 Low: 180 - 220 in 1V steps

 High: 240 - 264 in 1V steps

Intervention

sensitivity for

ECO

Selects the intervention
sensitivity during operation
in ECO mode

Normal

 Low

 Normal

 High

Power-on delay

Waiting time for automatic
switching back on after
mains power returns

5 sec.

 Disabled

 (1 - 255) sec. in 1 sec steps

Remote power-

on/off function

Selects the function
associated with the RS232
connector.

Disabled

 Disabled

 Remote ON

 Remote OFF

 Remote ON/OFF