Riello UPS Sentinel Pro (700 - 3000 VA) User Manual

Page 23

Advertising
background image

23

Active commands: Indicates the presence of an active remote command.

CODE

DESCRIPTION

C01

Remote control 1 (Switch On/Off)

C02

Remote control 2 (load on bypass or manual bypass command)

C03

Remote control 3 (Switch On/Off)

C04

Battery test in progress



L

OCK

LOCK alerts are normally preceded by an alarm signal and their scale leads to the power-off of the inverter and the load
being powered by the bypass line (this procedure is excluded for locks due to serious, persistent overloads and short
circuits).

CODE

DESCRIPTION

L02

Control card is not inserted correctly

L03

Incorrect auxiliary power supply

L04

Dissipator over temperature

L05

Temperature sensor1 faulty

L07

Temperature sensor2 faulty

L10

Input fuse broken or input relay stuck (does not close)

L11

Input relay faulty

L13

Capacitor pre-charge failed

L20

Capacitor bank undervoltage

L21

Capacitor bank overvoltage

L40

Inverter overvoltage

L41

Continuous output voltage

L42

Incorrect inverter voltage

L43

Inverter undervoltage

L50

Overload: load > 103%

L51

Overload: load > 110%

L52

Overload: load > 150%

L53

Short circuit


Advertising
This manual is related to the following products: