MS6 REDUCED VOLTAGE STARTER

Page 13

3 TERMINALS

CONTROL POWER INPUT
1

Control Power Line 1 (120VAC

± 10%)

2

Control Power Neutral

Power for the control card and also for
the cooling fans on units below 500A

120VAC INPUT LOGIC
3

Start Input – 120VAC

Momentary normally open switch for 3
wire control. Maintained normally open
switch for 2 wire control

4

Stop Input(three wire control) / DCI or
Soft Stop Enable(two wire control) -
120VAC

Momentary normally closed switch for 3
wire control. Maintained normally open
switch used to enable or disable a
selected stop mode in 2 wire control.

5

Jog Input – 120VAC

Maintained normally open switch used
to activate jog function

6

Reverse Input – 120VAC

Maintained normally open switch used
to activate reverse function (if installed).
If activated along with JOG the unit will
run in reverse jog mode

7

Reset Input – 120VAC

Momentary normally open switch use to
reset a fault

8

Enable Input – 120VAC

Maintained normally open switch used
to enable unit operation. Unit will not
run if this input is not active. If opened
while running the unit will coast to a
stop no matter what stopping method is
choosen. If this input is active and all 3
incoming phases are valid a green
indicator will be illuminated on the
keypad.

9

Input Neutral

Neutral for 120VAC control signals