MS6 REDUCED VOLTAGE STARTER

Page 27

15

Faults

1501

Shear Pin Flt
-

Enables and disables the shear pin fault

-

The shear pin fault is automatically disabled during jog

Enable
Disable

Read\Write

1502

MOL

Flt

-

Sets up the class of overload that will be used

-

Can also disable the overload

Disable
Class 10
Class 15
Class 20
Class 30

Read\Write

1503

Overload

Level

-

Represents has a percentage the amount of overload that has
accumulated

-

Once this level reaches 100% the Opal will trip on a MOL FLT

-

this level will increase based on the class set in parameter 1502 any
time that the current feedback is above the name plate current
(parameter 1301) multiplied by the service factor (parameter 1303)

-

this level will decrease any time that the current feedback is below
that level

-

if this level reaches 100% and the drive trips, a reset will not be
allowed until this level has decreased to 15%

Read

Only

1504

Comm

Flt

-

this will enable or disable the communication fault if a
communication module is present

-

a communication fault is detected by monitoring a watch dog bit
that the Opal sends out to the master device which has to be
inverted and sent back with in a specific amount of time (parameter
1505)

Enable
Disable

Read\Write

1505

Comm Flt Time
- this is the time used to determine a communication fault

0.1 – 5.0
seconds

Read\Write