Environment, Adjustments, Protection – SAF OPAL LT User Manual

Page 10: Indications, Temperatures, Mechanical, Output relay, Technical specification

Advertising
background image

Technical Specification


9

Environment

Supply voltage

Three phase, line to line,
380 – 415 Vac +10% -15%
460 – 500 Vac +10% -15% *
575 – 600 Vac +10% -15%

* 460 – 500 Vac is applicable for 220 – 240 Vac
by changing the position of the internal jumper –
J3. As shown in page 3.

Frequency

50 / 60 Hz

Load

Three-Phase, Three-Wire, Squirrel Cage
Induction Motor

Degree of protection

IP 20

Altitude

1000 m above sea level

Consult factory for derating

Adjustments

FLC (Full Load Current)

50% - 100%

Starting Torque (Initial Voltage)

10-50 % of full voltage

Current limit

100 % - 400% of nominal current

Ramp Up Time (soft start)

2 - 30 sec.

Ramp Down Time (Soft Stop)

0.2 - 30 sec.

Protection

Electronic Overload

Inverse time (I

2

t), factory preset at 115% of FLC, active only during Run.

Phase Loss

Trips when one phase is missing (When Neutral is connected)

Heatsink Over temperature

Trips when the heatsink temperature exceeds 85ºC.

Reset buttons

To reset the starter, after the fault has been removed.

Indications

ON - Green

Lights when three phases are connected to the
RVS-AX.

Ramp Up / Ramp Down – Yellow

Lights upon start signal or during soft stopping.

Indication lights (LEDs)

RUN – Green

Lights upon end of starting. When the internal
bypass relays close.

Overload – Red

Inverse time electronic overload becomes
operational after the End Of Acceleration process
(see page 7).

Phase loss – Red

Lights when one or two phases are missing for
more than 1 sec.

Over temperature – Red

Lights on and trips the starter when the heatsink
temperature rises above 85ºC.

Temperatures

Operating

-10° to 40°C

Storage

-20° to 70°C

Relative humidity

93 % - non condensed


EMC

Immunity to radio electric interference

EN 1000-4-3 level 3

Conforming to EN 60947-4-2

Electrostatic discharge

EN 1000-4-2 level 3

Conforming to EN 60947-4-2

Immunity to electrical transients

EN 1000-4-4 level 4

Conforming to EN 60947-4-2

Shock waves of voltage / current

EN 1000-4-5 level 3

Conforming to EN 60947-4-2

Radiated and conducted emissions

EN 1000-4-6 level 3

Radio frequency emissions

According to EN 55011 class A

Conforming to EN 60947-4-2

Mechanical

Shock resistance

8 gn

Conforming to EN 60947-4-2

Vibration resistance

2 gn

Conforming to EN 60947-4-2

Output relay

End of Acceleration Contact

N.O.

Rated operating current

5 A, 250 V - Size A1
8 A, 250 V – Size A2