Soft-start characteristics, Soft-stop characteristics, Rvs-ax ratings and frame sizes – SAF OPAL LT User Manual

Page 4: Starter selection

Advertising
background image

Starter Selection


3

The RVS-AX electronic soft starter incorporates six
thyristors to start a three-phase squirrel cage induction
motor. By supplying a slowly increasing voltage, it
provides soft start and smooth stepless acceleration,
while drawing the minimum current necessary to start
the motor.


A Soft Stop feature can be enabled when the Ramp-
Down potentiometer is adjusted. When used, upon stop
signal (open contact terminals 1 and 2), motor's voltage
is slowly reduced to zero.

Soft-Start Characteristics

M%

Torque

I%

U%

Current

Voltage

100

100

400

10

50

100

Soft-Stop Characteristics

The Soft-Stop characteristic
may be used for controlled
deceleration of pumps and high
friction loads.




RVS-AX ratings and Frame sizes

Max. Motor
FLA (Amp)

Starter Type
FLC (Amp.)

Frame Size

(A

luminum

)

8

RVS-AX 8

17

RVS-AX 17

31

RVS-AX 31

44

RVS-AX 44

A1

58

RVS-AX 58

72

RVS-AX 72

A2

85

RVS-AX 85

105 RVS-AX

105

A3

145 RVS-AX

145

170 RVS-AX

170

A4


Dimensions (mm) & Weights (Kg)

Size

Width

Height

Depth

Weights (Kg)

A1 120 232 105

2.6

A2 129 275 185

5

A3 129 380 185

8.4

A4 172 380 195

11.8

The starter should be selected in accordance with the
following criteria:

1. Motor Current & Starting Conditions
Select the starter according to motor's Full Load
Ampere (FLA) - as indicated on its nameplate (even if
the motor will not be fully loaded).
The RVS-AX is designed to operate under the
following maximum conditions:

Ambient

Temp.

I start

Acc. Time

300% In

30 Sec

350% In

20 Sec

40° C

400% In

5 Sec

Max.

Starts

per

Hour: four (4) starts per hour at

maximum ratings and up to 10
starts per hour at light load
applications (consult factory).

Note

: For very frequent starts (inching applications)

the inching current should be considered as the
Full Load Current (FLC) – consult factory.

2. Mains Voltage

U%

Voltage

10

50

100

Each starter is factory set for one of the following
levels according to the Ordering Information.

Voltage

Tolerance

380 - 415 V

+10 -15 %

440 V

+10 -15 %

460 - 500 V *

+10 -15 %

575 - 600 V

+10 -15 %

Frequency: 50 / 60 Hz.

* Starter’s rated 460-500VAC can be field modified

for system voltage of 220-240V, by placing the
internal Jumper J3 as shown below.


W

V

U

1 2 3

J3

1

2

3

1

2

3

220 to 240V

460 to 500V