2 optional features, 2 application notes, 1 operation modes – SAF OPAL SS6 User Manual

Page 9: 1 constant current mode, Optional features, Application notes, Operation modes

Advertising
background image

OPAL SS6 Reduced Voltage Starters

Page 2

1.1.2 OPTIONAL FEATURES

- Solid State Reversing

Through the addition of 4 Silicon Controlled Rectifiers ( SCR's ) and a reversing card,
smooth motor reversing is achieved without having to stop the motor.
- Soft Stop

Motor deceleration is controlled to eliminate water hammer effect on pump applications.

- By-Pass Contactor
Once the motor has reached operational speed, the by-pass contactor is closed. This shorts
the SCR's which eliminates the voltage drop across the SCR's, in turn being more efficient
and ridding excess heat.
- Up-To-Speed Contact / Shear Pin Protection / Energy Saver

- Shorted SCR Sensor and Protection
Sensor detects shorted SCR and trips circuit breaker or contactor upstream.

- Linear Accel\Decel Card

Provides linear accel and decel independent of load with the use of speed feedback

- DC Injection Braking
Through the addition of 4 SCR's and a DC Injection card, adjustable braking of an AC motor
is performed. More information is provided in the OP-STOP, DC INJECTION manual.

- External Reset Push Button

- Start, Stop, Reverse Push Buttons

- NEMA 4 or NEMA 12 Enclosures

1.2 APPLICATION NOTES

1.2.1 OPERATION MODES

1.2.1.1 Constant Current Mode

Applications

*Compressors

*Empty Mixers

*Empty Crushers

*Chippers

*Pumps/Fans

*Centrifuges

Advertising