All installations and services must be performed by qualified service personnel.

23

8. As a final step in the installation, the appliance must be adjusted to deliver a

temperature rise within the range of 50° to 80°F. Adjust the blower motor
speed to obtain a temperature rise within the acceptable range. The required
blower speed will depend on the airflow resistance of a supply and return air
duct systems.


I. Air

Filters


1. Filter Installation

This OPA unit has been factory supplied with a high quality, re-usable filter
rated for air velocities up to 600 ft/min.

2. Use of non-Thermo Pride Filters or Retention Means

: Failure to comply with minimum filter installation

requirements may affect the performance and/or void the warranty on
this unit.

If a method other than Thermo Pride filter racks is selected for retention of the
filter and/or use of a different filter type is desired, refer to Table 4 for
minimum sizing guidelines for selecting filter for the unit.

Table 4: Minimum Required Filter Area (in square inches)

Model Number

Filter Type

Maximum

Air Velocity

(ft/min)

OPA24 OPA30 OPA36 OPA42

*Thermo Products
Supplied
Permanent

600

192

240

288

336

Standard
Permanent

500

230

288

346

403

Disposable

300

384

480

576 672

∗ The Thermo Products supplied filter can be cut to size to fit other filter

retention systems as long as the minimum size requirement is met.

NOTICE: Any internal stiffeners used in the filter must not be removed,
although they can be cut to size as needed.