All installations and services must be performed by qualified service personnel.

66

This procedure can be repeated to determine the airflow for each room in the
residence. The results of these calculations are given in Table 6, below.


Table 6: Required Room Air Flowrates Based on Floor

Area for Example 2

We will assume the airflow is approximately equally split between all registers in
a particular room. This completes steps (a) through (d) of the duct sizing method.

For step (e), static pressure drops for each system, branch, and component must
be selected. Since the appliance circulating blower can only tolerate a maximum
pressure of 0.4 in. W.G., the combined resistance of the supply and return air
systems cannot exceed this amount.

Room

Room

Floor Area

(Sq. Ft.)

Room Air

Flowrate

(CFM)

Number of

Registers

Flowrate per

Register

(CFM)

Living

400

350

3

1 @ 120
2 @ 115

Dining

120

105

1

105

Kitchen

144

126

1

126

Master

Bedroom

360

315

2

2 @ 157

Bedroom

224

196

1

196

Bedroom

224

196

1

196

Master

Bathroom

64

56

1

56

Bathroom

64

56

1

56

Total

1600

1400

11