80

PROPER COMBUSTION ACHIEVED?

No

No

No

IS PUMP PRESSURE SET

ACCORDING TO BURNER

APPLICATION CHART

IS THE NOZZLE

PLUGGING?

No

IS BURNER SET TO

PRODUCE A TRACE

OF SMOKE AND

THEN "DETUNED".

IS WATER, DIRT, OR

SLUDGE PRESENT IN

THE OIL SYSTEM?

No

IS COMBUSTION AIR

Yes

TRY TO RAISE ROOM & OIL

IF THIS CANNOT BE DONE DO

THE FOLLOWING:

DECREASE NOZZLE SIZE AND

INCREASE PUMP PRESSURE.

CHOOSE SMALLER NOZZLE
SIZE AND PUMP PRESSURE

FROM "EFFECTS OF PRESSURE

ON NOZZLE FLOW RATES" AT

THE END OF THE TROUBLE

SHOOTING SECTION.

IS THE PROBLEM DELAYED

IGNITION?

ARE THE ELECTRODES

PROPERLY ALIGNED?

Yes

Yes

Yes

Yes

ADJUST TO 100-120 PSI

UNLESS COMBUSTION

AIR OR OIL BELOW 50

deg. F IS PRESENT (THIS

IS CONSIDERED BELOW)

ADJUST AIR TO A TRACE OF

SMOKE, THEN TAKE CO2 OR

O2 READING, NEXT SUBTRACT

1% FROM THE CO2 OR ADD 1%

TO O2 . THEN, ADJUST AIR TO

OBTAIN NEW CO2 OR O2 VALUES.

REPAIR OR REPLACE TANK

TO PREVENT FUTURE

PROBLEMS. MIX

IN PROPER ADDITIVES

TO REMOVE WATER

AND SLUDGE

Yes

Yes

No

CORRECT INSERTION OR

AIR TUBE BURNOFF

MAY OCCUR.

No

IS THE AIR TUBE INSERTION

0-1/4" BACK FROM INSIDE

OF REFRACTORY?

Yes

No

ALIGN ELECTRODES PER

BURNER INSTRUCTION

MANUAL SPECIFICATIONS

ARE VENT TERMINAL AND HEAT

EXCHANGER CLEAN?

Advertising