mer control at its maximum clockwise position set the output voltage to the desired
maximum value by adjusting the Vadj clockwise. The value should not be more than 110%
Eo nominal
.

By using an external 0-5.5V voltage source the maximum output voltage can be adjusted from 0 to

110%. For voltage source use remove the shorting link between the REF and RV terminal. Connect

the voltage source across the RV and (–)S terminals. The impedance of the load wires connecting

each power supply to the load should be the same when using remote sensing with this configura-

tion. It is possible that the overvoltage protection may be triggered if the external programming volt-

age source is changed very quickly when the power supply is at a low load condition

By adjusting the external control from minimum to maximum, the output voltage will change from

minimum to maximum value (0% to 110% of Eomax).

NOTE: Specifications are met when voltage is within adjustment range in Table 1. If remote

voltage control is not implemented, the shorting link between RV and REF must be in
place:

FIGURE 7 CONNECTIONS FOR REMOTE VOLTAGE CONTROL OF THE RCW 1500W POWER SUPPLY

3.6 REMOTE TURN-ON TURN-OFF

When power is ON at the source, the output may be turned ON or OFF with the remote control fea-

ture. The remote ON/OFF RC (Remote Control) terminals can be controlled by a logic level (2.4V

to 24V "high" and 0.0 to 0.4V "low"), or a contact closure. When the RC terminals (on the front

panel) are short circuited by using either a mechanical switch or a low level logic signal, the RCW

1500W output is cut OFF. At low level logic, the maximum sink current is 1.6mA. With the RC termi-

nals open the RCW 1500W output returns to within specifications. The RC terminals should remain

open if not used (see Figure ).

The RC terminals are isolated from the AC input and DC output terminals.