Configuring the MVI56E-MCMR Module

MVI56E-MCMR ♦ ControlLogix Platform

User Manual

Modbus Communication Module with Reduced Data Block

Page 58 of 225

ProSoft Technology, Inc.

May 13, 2014

The following parameters are displayed when the Type parameter is set to
M

ASTER

.

The following table describes the parameters in the E

DIT

M

ODBUS

P

ORT

1

dialog box when the Type parameter is set to M

ASTER

.

Parameter

Description

Enabled

1

=

ENABLE PORT

, 0 = disable port

Type

0

=

M

ASTER

, 1 = Slave

Protocol

0

=

M

ODBUS

RTU

MODE

, 1 = Modbus ASCII mode

Baud Rate

Sets the baud rate for the port. Valid values for this field are 110, 150,
300, 600, 1200, 2400, 4800, 9600, 19200, 384 or 3840 (for 38,400
baud), 576 or 5760 (for 57,600 baud) and 115,1152, or 11520 (for
115,200 baud)

Parity

0 = None, 1 = Odd, 2 = Even

Data Bits

Modbus RTU mode = 8 Modbus ASCII mode = 8 or 7

Stop Bits

Valid values are 1 or 2.

RTS On

0 to 65535 milliseconds to delay after RTS line is asserted on the port
before data message transmission begins. This delay can be used to
allow for radio keying or modem dialing before data transmission
begins.

RTS Off

0 to 65535 milliseconds to delay after data message is complete
before RTS line is dropped on the port.

Use CTS Line

N

O

or Y

ES

This parameter is used to enable or disable hardware handshaking.
The default setting is N

O

hardware handshaking, CTS Line not used.

Set to N

O

if the connected devices do not need hardware

handshaking. Set to Y

ES

if the device(s) connected to the port require

hardware handshaking (most modern devices do not). If you set this
parameter to Y

ES

, be sure to pay attention to the pinout and wiring

requirements to ensure that the hardware handshaking signal lines are
properly connected; otherwise communication will fail.