Diagnostics and Troubleshooting

MVI71-MNET ♦ PLC Platform

User Manual

Modbus TCP/IP Interface Module


ProSoft Technology, Inc.

Page 53 of 109

June 23, 2009

4.2

LED Status Indicators

The LEDs indicate the module’s operating status as follows:

ProSoft
Module

Color Status Indication

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

CFG Green

Off

No data is being transferred on the Configuration/Debug port.

On

Port not used

P1 Green

Off

Port not used

On

Port not used

P2 Green

Off

Port not used

Off

The MVI71-MNET is working normally.

APP Amber

On

The MVI71-MNET module program has recognized a
communication error on one of its Modbus ports.

On

The LED is on when the module is performing a write
operation on the backplane.

BP ACT

Amber

Off

The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the LED
should blink rapidly on and off.

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

OK Red/

Green

Red

The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and re-insert
the card to restart the module’s program.

Off

The battery voltage is OK and functioning.

BAT Red

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.

If a configuration error is found for the client, the client configuration error word
will have a value other than zero. The configuration error word bits have the
following definitions:

Bit Description

Value

0

0x0001

1

0x0002

2

0x0004

3

0x0008

4

Invalid retry count parameter

0x0010

5

The float flag parameter is not valid.

0x0020

6

The float start parameter is not valid.

0x0040

7

The float offset parameter is not valid.

0x0080

8

0x0100

9

0x0200