Diagnostics and Troubleshooting

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

8.2

LED Indicators

The LEDs indicate the module’s operating status as follows:

LED

Color

Status

Indication

PRT1

Green

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

Off

No data is being transferred on the Configuration/Debug port.

PRT2

Green

On

Port not used in application

Off

Port not used in application

PRT3

Green

On

Port not used in application

Off

Port not used in application

ERR1

Red

Off

The PTQ-104S is working normally.

On

The PTQ-104S module program has recognized an application
error.

ERR2

N/A

Not used in application

ERR3

Red

On

Configuration Error

Active

Green

On

The LED is on when the module recognizes a processor and is
able to communicate if the [Backplane Data Movement] section
specifies data transfer commands.

Off

The LED is off when the module is unable to speak with the
processor. The processor either absent or not running.

BAT

Red

Off

The battery voltage is OK and functioning.

On

The battery voltage is low or the battery is not present. The battery
LED will illuminate briefly upon the first installation of the module or
if the unit has been un-powered for an extended period of time.
This behavior is normal, however should the LED come on in a
working installation please contact ProSoft Technology.

If your module is not operating, and the status LEDs are not illustrated in the
table above, please call ProSoft Technology for technical assistance.

8.2.1 Ethernet LED Indicators

LED

State

Description

Data

Off

No activity on the Ethernet port.

Green Flash

The Ethernet port is actively transmitting or receiving data.

Link

Off

No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.

Green Solid

Physical network connection detected. This LED must be on
solid for Ethernet communication to be possible.

8.2.2 Error Status Table

The program maintains an error/status table that is transferred to the processor
in each read block. You can use the error/status data to determine the "health" of
the module. Refer to Error Status Table (page 176) for data block structure.

Page 126 of 201

ProSoft Technology, Inc.

March 4, 2013