ProSoft Technology 5301-MBP-ASCII User Manual

Page 26

Advertising
background image

MBP Protocol Configuration

MBP ♦ ProLinx Gateway

Protocol Manual

Modbus Plus

Page 26 of 52

ProSoft Technology, Inc.

May 12, 2011

3.3

[Modbus Plus Commands]

The [Modbus Plus Commands] sections defines the commands to issue from the
module to other devices on the Modbus Plus network. Commands are entered in
the columns between the START and END labels. This section may contain up to
200 commands.

Example

Parameter Description
The following section lists the parameters.

3.3.1 Enable

This field defines how to execute the command:
 Disable (0): disables the command. The command will not execute during the

normal polling sequence.

 Continuous (1): executes the command during each scan of the command list

if the Poll Interval Time is set to zero (0). If the Poll Interval Time is set, the
command will be executed when the interval timer expires.

 Event Command (2): The command executes only if the internal data

associated with the command changes. This value is only valid for WRITE
commands.

3.3.2 Internal Address

0 to 3999
This field specifies the internal database register to be associated with the
command.
 If the command is a read function, the data read from the slave device will be

placed starting at the register value entered in this field.

 If the command is a write function, the data written to the slave device will be

sourced from the address specified.