Example 2 - Command Request with Response Only
For this example, the remote node is requesting the event buffer sizes from the

ProLinx gateway. This is an example of a request that requires a response back

from the gateway:

The following block can be used for the first request.

Command Request Block

Word Offset Database

Address

Value

Description

0

3000

0

Block ID1 - Command Request Without Response

Move a value of 0 or any other value out of the 100

to 101 and 200 to 201 range, because no request

without response is performed

1

3001

202

Block ID2 - Command Request With Response.

2 to 98

3002 to 3098 Not Used

Not Used

99

3099

0

Block ID1 - Command Request Without Response

Move a value of 0 or any other value out of the 100

to 101 and 200 to 201 range, because no request

without response is performed


Command Response Block

Word

Offset

Database

Address

Value

Description

0

3100

202

Block ID2 - Command Request With Response.

1

3101

0

Block ID1 - Command Request Without Response

2 to 8

3102 to 3108 Event Buffers Event Buffers

99

3199

202

Block ID2 - Command Request With Response.

In order to send another command request to pass another event, use the

following format: