Events – ProSoft Technology 5201-MNET-101S User Manual

Page 99

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 99 of 159

August 6, 2010

5.2.6 Events

In order to improve the communication efficiency, most applications will require

the Master to periodically poll for data changes with a higher priority than polling

for monitor data. Every time data change occurs, the slave should send this

information, typically with the date and time information on when the data change

occurred.

The following illustration shows the event communication between the Master

and the gateway during unbalanced mode:

The gateway can queue up to 99 events per data type. When the queue is full,

the oldest event will be deleted each time a new event is added to the queue.

You must configure the Master to poll the event queue frequently enough to

avoid losing events.

Advertising
This manual is related to the following products: