2.4 Environment Requirement

Item

Requirement

Rack Space

When installing unit on rack, the distance between 2 rows of
machine frames should be 1.2~1.5m and the distance against
wall should be no less than 0.8m.

Rack Room

Electric Isolation, Dust Free, HVAC

anti-static

material:1X10

7

~1X10

10

,

Grounding

current

limiting resistance: 1M

(Floor bearing should be greater than

450Kg/

)

Environment
Temperature

5~40

(sustainable )

0~45

(short time)

installing air-conditioning is recommended

Relative Humidity

20%~80% sustainable 10%~90% short time

Pressure

86~105KPa

Door & Window

Installing rubber strip for sealing door-gaps and dual level
glasses for window

Fire Protection

Fire alarm system and extinguisher

Power

Device power, HVAC and lighting should be independent to
each other. Device power requires AC 110V±10%, 50/60Hz or
AC 220V±10%, 50/60Hz. Please carefully check before
running.